Air Conditioning Systems
DMAM Series
Technical Specifications
| Type (Cooling) |
|---|
| Indoor Unit |
| DMAM-48KVR-Y1 |
| Outdoor Unit |
| DMBM-48KPR-Y1 |
| Performance Parameters | |||
|---|---|---|---|
| Cooling | Power supply | 230+/-10%-1-50 V,Hz,Ph | |
| Cooling Capacity | 14068 W | ||
| Input | 5100 Watts | ||
| Current | 9.4 A | ||
| Indoor coil | Number of rows | 3 | |
| Fin type (code) | Hydrophilic aluminium | ||
| Tube outside dia.and type | ?7, inner groove tube mm | ||
| Indoor air flow (Hi/Med/Lo) | 2612/2292/2088 m3/h | ||
| ESP | Rated | 50 pa | |
| Sound level (sound pressure) | 53/49/42 dB(A) | ||
| Indoor unit | NET Dimension(WxDxH) | 1200x725x345 mm | |
| Packing (WxDxH) | 1420x760x370 mm | ||
| Net/Gross weight | 50 / 54 Kg. | ||
| Drainage water pipe dia. | 0D?25mm | ||
| Refrigerant piping | Liquid side/ Gas side | ?9.52/?19(3/8"/3/4") mm |
|
| Controller | Wired control | ||
| Operation temperature | Cooling | 17~30 0c | |
| OUTDOOR UNIT | |||
|---|---|---|---|
| Power supply | 400+/-10%-3-50 | V-Ph-Hz | |
| Compressor | Type | Scroll | |
| Outdoor coil | Number of rows | 3 | |
| Tube outside dia. and type | ?7, inner grooved tube | mm | |
| Outdoor noise level | 64 | dB(A) | |
| Outdoor unit | Dimension (WxHxD) | 910X820X320 | mm |
| Packing WxHxD' | 1022X897X424 | mm | |
| Net/ Gross weight | 70/73 | Kg | |
| Refrigerant type/Quantity | Type | R410A / 20 0 | Gms |
| Refrigerant piping | Liquid side/ Gas side | ?9.52/?19(3/8"/3/4") | mm |
| Max. pipe length | 30 | m | |
| Max. difference in level | 10 | m | |
| Ambient temperature | Cooling | 18~50 | 0c |
Where to buy