Air Conditioning Systems

S Series Cooling Only

Total Capacity / Model Name

Technical Specifications

Model Name PUMY-CP250YBM PUMY-CP300YBM
Power Source 3-phase 380-400-415V 50Hz / 380V 60Hz
Cooling Capacity(Nominal) kW 28.0 33.5
Btu 95500 114300
  Power Input kW 7.18 8.59
  Current Input A 11.73-11.14-10.74, 11.73 14.03-13.33-12.85, 14.03
  EER kW/kW 3.90 3.90
Temp. range of cooling Indoor W.B. 15 to 24°C (59 to 75°F)
Outdoor D.B. 10 to 52°C (50 to 126°F)
Indoor unit connectable Total capacity 50 to 150% of outdoor unit capacity *2
Model/Quantity CITY MULTI 15-250/24 15-250/29
Sound pressure level
(measured in anechoic room)
dB(A) 59 60
Refrigerant piping diameter Liquid pipe mm(in.) 9.52(3/8) Flared *5 12.7(1/2) Flared
Gas pipe mm(in.) 22.2(7/8) Brazed 25.4(1) Brazed
FAN Airflow rate m3/min 178 178
L/s 2966 2966
cfm 6285 6285
Type x Quantity   Propeller Fan x 2
Motor Output kW 0.375 + 0.375
Compressor Type x Quantity Scroll hermetic compressor X 1
Starting Method Inverter
Motor Output kW 6.77 7.59
External Dimension HxWxD mm 1,662 X 1,050 x 460 (+45)
in. 65-7/16 * 41-11/32 x 18-7/64 (+1-49/64)
 Protection devices High pressure protection High pressure switch

Inverter circuit
(COMP./FAN)

Overcurrent detection, Overheat detection (Heat Sink thermistor)
Compressor Compressor thermistor, Overcurrent detection, Compressor protector
Fan motor Overcurrent, Overheating, Voltage protection
Refrigerant Type x original charge   R410A 8.0kg
Net weight kg/lbs 185(408) *4
External finish Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
Heat Exchanger Micro-Slit Fin and Copper tube
Optional parts Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
  • *1 Nominal conditions
  •   Indoor Outdoor Pipe length Level difference External Static Press
    Cooling 27ºC DB/19ºC WB
    (81ºF DB/66ºF WB)
    35ºC DB (95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.) 0 Pa
  • *2 Up to 150% can be connected. However, up to 130% for simultaneous operation.
  • *3 External static pressure option is available (30 Pa/3.1 mmH2O).
  • *4 187kg(413lbs) for PUMY-CP250/300YBM-BS.
  • *5 Liquid pipe diameter: 12.7mm, in case of farthest piping length (farthest indoor unit from outdoor unit) is longer than 90m, or connect with PEFY-P200/250.
  • *Nominal conditions *1 are subject to ISO 15042.
  • Due to continuing improvement, above specification may be subject to change without notice.

Where to buy

Our range of air conditioners, now within your reach

Service & Support