Air Conditioning Systems

S Series Heat Pump

Total Capacity / Model Name

Technical Specifications

 
Model Name PUMY-P250YBM (-BS) PUMY-P300YBM (-BS)
Power Source 3-phase 380-40-415V, 50 Hz; 3 phase 380 V, 60 Hz
Cooling Capacity 
(Nominal)
kW *1 28.0 33.5
Btu *1 95500 114300
  Power Input kW 6.83 8.17
  Current Input A 11.16-10.60-10.22, 11.16 13.35-12.68-12.22, 13.35
  EER kW/kW 4.1 4.1
Temp. range of cooling Indoor temp. W.B. 15.0 to 24.0°C (59 to 75°F)
Outdoor temp. *3*4 D.B. -5.0~52.0°C (23 to 126°F)
Heating Capacity 
(Nominal)
kW *2 31.5 37.5
Btu *2 107400 127900
  Power Input kW 6.06 7.36
  Current Input A 9.90-9.41-9.07, 9.90 12.02-11.42-11.01, 12.02
  COP kW/kW 5.2 5.1
Temp. range of heating Indoor temp. D.B. 15.0 to 27.0°C (59 to 81°F)
Outdoor temp. W.B. -20.0 to 15.0°C (-4 to 59°F)
Indoor unit connectable Total capacity 50 to 130% of outdoor unit capacity
Model/Quantity CITY MULTI 15–250/21 15–250/25
Sound pressure level
(measured in anechoic room)
dB(A) 59/60 60/62
Refrigerant piping diameter Liquid pipe mm(in.) 9.52(3/8) Flared *8 12.7(1/2) Flared
Gas pipe mm(in.) 22.2(7/8) Brazed 25.4(1) Brazed
FAN Air flow rate m3/min 187/183 187/197
L/s 3116/3050 3116/3283
cfm 6603/6462 6603/6956
Type x Quantity Propeller Fan × 2
Motor Output kW 0.375 + 0.375
Compressor Type x Quantity Scroll hermetic compressor × 1
Starting Method Inverter
Motor Output kW 6.65 7.35
External finish Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
External Dimension HxWxD mm 1,662 × 1,050 × 460 (+45)
in. 65-7/16 × 41-11/32 × 18-7/64 (+1-49/64)
Protection Devices High pressure protection High pressure switch
Inverter circuit 
(COMP./FAN)
Overcurrent detection, Overheat detection (Heat Sink thermistor)
Compressor Compressor thermistor, Overcurrent detection, Compressor protector
Fan motor Overcurrent, Overheating, Voltage protection
Refrigerant Type x original charge R410A 9.3kg
Net weight kg/lbs 192 (424) *7
Heat Exchanger Ring Fin and Copper tube
Defrosting method Reversed refrigerant circuit
Optional parts Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
  • *1,*2 Nominal conditions
  •   Indoor Outdoor Pipe length Level difference
    Cooling 27ºC DB/19ºC WB
    (81ºF DB/66ºF WB)
    35ºC DB (95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.)
    Heating 20ºC DB (68ºF DB) 7ºC DB/6ºC WB (45ºF DB/43ºF WB) 7.5 m (24-9/16 ft) 0m (0ft.)
  • *3 10 to 52ºC D B. When Connecting PKEY-P15/20/25/32VLM,PFFY-P20/25/32VLEM,PFFY-P20/25/32VLRM(M),PFFY-P20/25/32VCM,PFFY-P-VMA3, M, S and P series indoor unit.
  • *4 -15 to 52ºC D.B. [5 to 126ºF D.B.], when using an optional air protect guide [PAC-SH21AG-E]. However, this condition does not apply to the indoor unit listed in*3.
  • *5 Cooling mode/Heating mode
  • *6 External static pressure option is available (30 Pa/3.1 mmH2O).
  • *7 194 (428) for PUMY-P250/300YBM-BS.
  • *8 Liquid pipe diameter: 12.7mm, in case of farthest piping length (farthest indoor unit from outdoor unit) is longer than 90m, or connect with PEFY-P200/250.
  • *Nominal conditions *1,*2 are subject to ISO 15042.
  • *Dueto continuing improvement, above specification may be subject to change without notice.