Air Conditioning Systems

S Series Cooling Only

Total Capacity / Model Name

Technical Specifications

Model Name PUMY-CP100VKM PUMY-CP125VKM PUMY-CP140VKM
Power Source 1-phase 220-230-240 V, 50 Hz; 1-phase 220 V, 60 Hz
Cooling Capacity(Nominal) kW 11.20 14.00 15.50
Btu 38200 47800 52900
  Power Input kW 2.80 3.84 4.70
  Current Input A 12.99-12.42-11.90, 12.99 17.81-17.04-16.33, 17.81 21.80-20.85-19.98, 21.80
  EER kW/kW 4.00 3.65 3.30
Temp. range of cooling Indoor W.B. 15 to 24°C (59 to 75°F) 15 to 24°C (59 to 75°F) 15 to 24°C (59 to 75°F)
Outdoor D.B. 10 to 52°C (50 to 126°F) 10 to 52°C (50 to 126°F) 10 to 52°C (50 to 126°F)
Indoor unit connectable Total capacity 50 to 130% of outdoor unit capacity
Model/Quantity CITY MULTI 15-125/7 15-140/10 15-140/12
Sound pressure level *2
(measured in anechoic room)
dB(A) 52/- 53/- 54/-
Refrigerant piping diameter Liquid pipe mm(in.) 9.52(3/8) 9.52(3/8) 9.52(3/8)
Gas pipe mm(in.) 15.88(5/8) 15.88(5/8) 15.88(5/8)
FAN Airflow rate m3/min 78.8
L/s 1313
cfm 2782
Type x Quantity   Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Motor Output kW 0.20 x 1
Compressor Type x Quantity Twin rotary hermetic compressor × 1
Starting Method Inverter
Motor Output kW 2.2 2.7 3.0
External Dimension HxWxD mm 981x1050x330(+25) 981x1050x330(+25) 981x1050x330(+25)
in. 38-5/8 × 41-3/8 × 13 (+1) 38-5/8 × 41-3/8 × 13 (+1) 38-5/8 × 41-3/8 × 13 (+1)
 Protection devices High pressure protection High pressure switch

Inverter circuit
(COMP./FAN)

Overcurrent detection, Overheat detection (Heat Sink thermistor)
Compressor Compressor thermistor, Overcurrent detection
Fan motor Overheating, Voltage protection
Refrigerant Type x original charge   R410A 2.9kg
Net weight kg/lbs 86(190) *4 86(190) *4 86(190) *4
External finish Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1 Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1 Galvanized Steel Sheet Munsell No. 3Y 7.8/1.1
Heat Exchanger Micro Slit Fin and Copper tube Micro Slit Fin and Copper tube Micro Slit Fin and Copper tube
Optional parts Joint: CMY-Y62-G-E, Header: CMY-Y64/68-G-E
  • *1 Nominal conditions
  •   Indoor Outdoor Pipe length Level difference
    Cooling 27ºC DB/19ºC WB
    (81ºF DB/66ºF WB)
    35ºC DB (95ºF DB) 7.5m (24-9/16ft.) 0m (0ft.)
  • *2 Cooling mode/Heating mode.
  • *3 External static option is available(30Pa/3.1mmH2O.)
  • *4 87 (192), for PUMY-CP100/125/140VKM.TH-BS. 88 (195), for PUMY-CP100/125/140YKM.TH-BS.
  • *Nominal conditions *1 are subject to ISO 15042.
  • *Due to continuing improvement, above specification may be subject to change without notice.
  • *This unit cannot be connected with the PFFY-YM-E or PFFY-YMH-E.